Description

The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.

INFO

Published Date :

2026-03-12T20:06:05.753Z

Last Modified :

2026-03-12T20:06:05.753Z

Source :

icscert
AFFECTED PRODUCTS

The following products are affected by CVE-2026-3611 vulnerability.

No data.

REFERENCES

CVSS Vulnerability Scoring System

Detailed values of each vector for above chart.
Attack Vector
Attack Complexity
Attack Requirements
Privileges Required
User Interaction
VS Confidentiality
VS Integrity
VS Availability
SS Confidentiality
SS Integrity
SS Availability
Detailed values of each vector for above chart.
Attack Vector
Attack Complexity
Privileges Required
User Interaction
Scope
Confidentiality Impact
Integrity Impact
Availability Impact