Description
A vulnerability has been identified in APOGEE PXC+TALON TC Series (BACnet) (All versions). Affected devices start sending unsolicited BACnet broadcast messages after processing a specific BACnet createObject request. This could allow an attacker residing in the same BACnet network to send a specially crafted message that results in a partial denial of service condition of the targeted device, and potentially reduce the availability of BACnet network. A power cycle is required to restore the device's normal operation.
INFO
Published Date :
2025-05-13T09:38:50.440Z
Last Modified :
2025-05-13T13:25:06.076Z
Source :
siemens
AFFECTED PRODUCTS
The following products are affected by CVE-2025-40555 vulnerability.
No data.
REFERENCES